Conductivity & TDS Controller KE - CD 1000


INTRODUCTION
CD1000 Series Controller is a microprocessor-based controller used to analyze and control Conductivity / TDS parameter in various water applications. CD 1000 provides set point values and relay for High-Low signal. Usually it doesn’t require any calibration but only 1-point calibration if required.

CD 1000 series is simple to control through its 6-button control panel. The backlit LCD contrast can be adjusted to user requirement. Provided logging function can save parameters values with respect to time.

APPLICATIONS
• REVERSE OSMOSIS
• BOILER WATER
• COOLING WATER
• CLOSED LOOP SYSTEM
• DRINKING WATER
• TEXTILES CHEMICALS
• WASTE WATER













×

Description


INTRODUCTION
CD1000 Series Controller is a microprocessor-based controller used to analyze and control Conductivity / TDS parameter in various water applications. CD 1000 provides set point values and relay for High-Low signal. Usually it doesn’t require any calibration but only 1-point calibration if required.

CD 1000 series is simple to control through its 6-button control panel. The backlit LCD contrast can be adjusted to user requirement. Provided logging function can save parameters values with respect to time.

APPLICATIONS
• REVERSE OSMOSIS
• BOILER WATER
• COOLING WATER
• CLOSED LOOP SYSTEM
• DRINKING WATER
• TEXTILES CHEMICALS
• WASTE WATER

×
Specifications Descriptions
Measuring Range (Conductivity) 0.00 μS/cm - 10.00 S/cm, 0.01 μS/cm resolution, +/- 0.5% accuracy
Measuring Range (TDS) 0.00 - 10000 PPT, 0.01 PPM resolution, +/- 0.5% accuracy
Measuring Range (Temperature) 0.0-200.0°C, 0.1°C resolution, Linear Coefficient +/- 1.0°C accuracy
Clock Internal Clock, 24 Hr format, +/- 1 min / month accuracy
Logger Internal Logger can save up to 60 Conductivity & Temperature values with respective Time & Date
Calibration Mode Usually No Calibration is required but 1 point Calibration through any NIST or TCT standard buffers can be done if required
Analog Output 1 4-20mA corresponding to conductivity, +/- 0.1mA accuracy, 0.1mA resolution, maximum load 500Ω
Analog Output 2 4-20mA corresponding to temperature, +/- 0.1mA accuracy, 0.1mA resolution, maximum load 500Ω
Cell Constants 0.01 – 20 /cm fixed, 0.001 – 19.99 /cm freely selectable (user defined)
Relays 1 (HI) – 200 VDC, 0.5A – On/Off Programmable
2 (LO) – 200 VDC, 0.5A – On/Off Programmable
Display Large Graphical LCD (128x64) with adjustable Contrast and Adjustable Backlight
Dimensions (Volume Based) L x W x D (113.5mm x 113.5mm x 83mm)
Mounting Type Panel Mount
Panel Cutout Size L x W (93mm x 93mm)
Temperature Rectification 2-wire & 3-wire Pt1000 RTD auto/manual
Power Requirement +12 - 24 VDC (maximum up to 35 VDC)
Weight (Assembly) ≈ 255 Grams
IP Class Protection IP 65

×

Downloads


Compatible Products


Related Products

©  2018. RCB Chemicals & Services. All rights reserved.